Cast Iron Double Regulating and Commissioning Valve Confirms BS 5152 (EN 13789)
Y Pattern
Flanged to BS 4504/DIN PN 16 (EN1092) Variable Orifice with liner scale and circular scale (fine adjustment) Complies to BS 7350 requirements
Hand wheel embraces a vernier scale for accurate setting. Valves have unique design which enables the disc to be locked in the set- position with a screwdriver.
Valve is supplied with a screw driver secured to the hand wheel, Two points (inlet/outlet) are available on the body of the valve for fixing the- measuring nipples / test plugs for measurement of flow/delta P(balancing).
Hydrostatic Test Pressure
Body: 24 bar
Seat: 17.6 bar
Face to Face Dimensions
EN 558-1 Basic Series 1
Pressure / Temperature Rating
16 bar at -10 to 120 deg C
Maximum Differential Pressure
DN 65 DN 200 16 bar
DN 250: 6 bar
DN 300 4 bar
Material Specification
No.
Component
Material
DIN
BS
01
Body
Cast Iron
1691GG25
1561-GJL-250
02
Disc DN 65 - 200
CI + EPDM Coated
1691GG25
1561-GJL-250
02 a
Disc DN 250 & 300
SS + EPDM Ring
-
-
03
Disc Nut
Brass
X20Cr13
420S37
04
Stem
Stainless Steal
X10Cr13
410S21
05
O - Ring
EPDM
-
-
06
Bonnet
Cast Iron
1691GG25
1561-GJL-250
07
Gasket
Graphite
-
-
08
Hand Wheel
GGG40 + Epoxy Coating
-
-
09
Gland
Carbon Steel
-
-
10
Nut
Brass
-
-
11
Position Indicator
Plastic
-
-
12
Adjusting Bolt
Brass
-
-
13
Bolt
Carbon Steel
-
-
Dimensions & Weights
Nominal Size
Dimensions
Weight
D(mm)
D(mm)
L(mm)
H(mm)
KG
65
180
290
293
18.0
80
180
310
305
23.0
100
180
350
323
33.5
125
250
400
353
49.0
150
250
480
388
62.0
200
250
600
453
96.0
250
420
730
575
195.0
300
420
850
645
315.0
Balancing Valve Thd
Brass Double Regulating Valve
Features:
PN 25
Variable Orifice
Bronze Double Regulating and Commissioning Valve
Y Pattern
Threaded ends to BS 21 (BSPP)
Variable Orifice with liner scale and circular scale (fine adjustment) Maintenance free valve.
Low flow resistance due to unique design.
Complies to BS 7350 accuracy requirements.
Tight closure of valve is assured by use of PTFE disc insert.
Hand wheel embraces a vernier scale for accurate setting.
Valves have unique design which enables the disc to be locked in the set position.
Valve can be sealed in the set position with the sealing wire and lead seal.
Two ports (inlet/outlet) are available on the body of the DRV (Fig: 2601V).
These points are for fixing the measuring nipples or test plugs for the- measurement of flow/delta P (balancing).